Troubleshooting Chart 3

CHECK FOR VAC

BETWEEN TERMINALS 1 AND 3

AT CONNECTOR CN4 ON IBC

NO

NO

BLOWER STARTS

REPLACE IBC

CHART 1

OPEN

IBC PURGE LIGHT ON?

NO

YES

IBC WAITS UP TO 5

MINUTES FOR NORMALLY

OPEN AIR

PRESSURE SWITCH

CONTACTS TO CLOSE,

INDICATING BLOWER

SUCTION IS

PRESENT

YES

CHECK FOR 120 VAC AT

BLOWER LEADS ON WIRING

HARNESS

YES

REPAIR/REPLACE

BLOWER

NO

REPAIR/REPLACE

WIRING FROM IBC

TO BLOWER

PRESSURE SWITCH

CONTACTS

OPEN

ARE VENT PIPE AND AIR

INTAKE PIPE CLEAR

(NO BLOCKAGE)

NO

CLEAN OUT VENT PIPE

AND/OR AIR INTAKE PIPE.

CHECK FOR SAGS OR

LOW SPOTS WHERE

CONDENSATE MAY

PUDDLE AND BLOCK

THE VENT

YES

CHECK AIR

PRESSURE SWITCH PER

INSTRUCTIONS ON

FOLLOWING PAGES. ARE

SAMPLING LINES CLEAR

AND CONNECTED

PROPERLY?

NO

CLEAN OUT SAMPLING

LINES OR REPLACE

DEFECTIVE SWITCH

YES

CHECK FLUE PASSAGES

IN BOILER PER

"MAINTENACE AND

CLEANING". ARE FLUE

PASSAGES IN BOILER CLEAN?

NO

CLEAN BOILER FLUE

PASSAGES PER

MAINTENANCE AND

CLEANING INSTRUCTIONS

YES

CHECK DRAFT INDUCER

MOTOR RPM. IS IT

3400-3600?

NO

REPLACE

BLOWER

YES

CHECK FOR BROKEN OR

LOOSE IMPELLER ON DRAFT

INDUCER AND REPLACE

BLOWER IF FOUND TO

BE BROKEN OR LOOSE

YES

15 SECOND PRE PURGE COMPLETE.

IBC PURGE LIGHT IS OFF. SIMULTANEOUSLY

IGNITOR LIGHT IS ON AS IGNITOR CIRCUIT

IS ENERGIZED.

YES

CHART 4

NO

REPLACE IBC

ARE ORIFICE IN

NEGATIVE PRESSURE

HOSE CLEAR?

NO

YES

CLEAN OUT BLOCKAGE

AT ORIFICE