Warning – Dunkirk Q90-200 Series II User Manual

Page 27

Advertising
background image

27

Differential Pressure Switches

• Diaphragm type differential pressure switches are

connected by vinyl tubing to gas valve, air inlet

connection on negative side, and sight glass adapter

on positive side. Pressure switches monitor air flow

by sensing differential pressure measured in inches of

water (” w.c.).

• Switch factory settings are 0.5” w.c. on normally open

switch and 3.5” w.c. for normally closed switch.

• See pages 31-32, “Detailed Sequence of Operation,” for

details.

Blower

Blower provides means for pushing combustion air into

and through mixer, burner, and flue ways of cast aluminum

boiler section before being discharged through vent piping

to outdoors.

Circulator Pump

• Forced hot water system requires at least one circulating

pump.

• Circulating pump provides energy to move water

through closed loop supply, return piping systems,

terminal heating equipment (finned tube radiators, etc.)

and back through boiler for reheating.

• To provide required hot water flow rates, circulator

pump must be properly sized to overcome frictional

losses (usually measured in feet of water, also referred

to as “pump head loss”) of supply and return piping

systems and boiler.

• Circulator pump is furnished in a carton within boiler

cabinet. Locate circulator(s) on downstream (i.e.,

“pumping away”) side of expansion tank.

Drain Valve

Manual drain valve is means of draining water in heating

system, including boiler, hot water supply and return piping

systems installed above drain valve.

Install drain valve in ¾” tapping at bottom of boiler.

Piping installed below drain valve elevation requires

additional drain valves installed at low points in piping

systems to drain entire system.

WARNING

Burn and scald hazard. Safety relief valve could

discharge steam or hot water during operation.

Install discharge piping per these instructions.

!

A.S.M.E. Rated Pressure Relief Valve

• Each boiler must have properly sized and installed

A.S.M.E. rated pressure relief valve.

• Water expands as it is heated by the burner/boiler

sections. If no place for water to expand its volume,

(i.e., properly sized functioning expansion tank)

pressure inside of boiler and heating system increases.

10 - CONTROLS AND ACCESSORIES

• Pipe pressure relief valve discharge with same size as

valve discharge opening to open drain, tub or sink, or

other suitable drainage point. Do not subject to freezing,

in accordance with A.S.M.E.

• Failure to provide pressure relief valve with piping as

described may cause water damage and/or serious

bodily injury.

Blocked Vent Safety Shutoff

• Boiler equipped with blocked vent safety shutoff, shuts

off main burner gas in event airflow of combustion

products through flue-way is reduced.

• Air will not be available to support combustion if flue-

way is blocked. IBC locks out due to loss of adequate

air flow.

• Pressure switches monitor air flow by sensing differential

pressure. Contacts normally open and close when draft

inducer is running causing differential pressure at switch

to exceed settings. Closed switch proves adequate air

flow for combustion.

• Pressure switch shuts off main burner if differential

pressure is inadequate due to blocked vent pipe, blocked

air intake, blocked boiler section, or blocked air inducer.

After 5 minutes of inadequate differential pressure, IBC

will lock out.

• “Purge” indicator lamp blinks, see Figure 19, Page 26,

indicating failure to prove adequate combustion air

flow or flue gas flow. IBC automatically resets after 15

minutes or manually reset as noted see “C” page 26

.

Boiler cannot be restored to normal operating condition

by resetting control, contact qualified service agency to

check heat exchanger flue-ways for blockage.

High Limit /Low Water Cut Off

Unit equipped with high limit low water cut off control,

protects against over temperature and dry firing. Control

provides burner cut off if unsafe water loss, which can

result from broken or leaking radiator, pipe, or boiler. Use

water/glycol mixture 50% with low water cut off.

Refer to manufacturer provided literature for specific

features.

External Condensate Pump (Optional)

Installations where no floor drain or other appropriate

drainage available, external float activated condensate pump

with integral sump (not supplied) is required.

May pipe condensate pump to remote tie in point to

sanitary sewer system. For this application, boiler must be

installed so proper pitch of piping to external condensate

reservoir (sump) can be accomplished. Use wood frame or

blocks to raise boiler as required for proper installation.

• Furnished relief valve automatically opens at 30 psi

to relieve strain on boiler and heating system from

increasing pressure.

Advertising