15 - TROUBLESHOOTING

Troubleshooting Flow Chart - High Limit Control And LWCO

Burner Will Not Fire See Flow Chart, this page.

No or Insufficient

Domestic Hot Water

If installed with indirect water heater, insure end switch in relay box controlling indirect water

heater is properly connected to Cable 2. This will insure domestic water calls are prioritized. If

Cable 2 is not used, turn Economy Feature OFF.

House Will Not Get or

Stay Warm

1.

Check for air-bound radiators.

2.

Check thermostat settings including heat anticipator settings (common on non-digital

thermostats).

3.

Check Economy setting. Economy feature, like outdoor reset controls, lowers average

boiler temperature and can slow or, in some cases, prevent the house from coming up to

temperature. Move to lower setting.

Is Red LED

(LOW WATER)

On?

Is Yellow LED

(HI TEMP)

On?

Is Yellow LED

(TARGET)

On?

Is

PURGE LED

on?

Replace

Control

Control is

Sensing Low

Water

Control is

Sensing High

Temperature

Boiler

Reached

Target

Temperature

Boiler in Purge Mode

and will not fire until

temperature drops to

140°F.

See Purge page 36.

Both red and yellow LEDs are off and there is call

to fire burner, there will be 120 VAC in terminals

B1 and B2.
►120 VAC is not present, replace control.

CAUTION- ALWAYS ALLOW BOILER TO COOL BEFORE

ADDING WATER

Burner will not fire until low water condition is satisfied.
►Verify system filled with water.
►Verify sensor is inserted correctly into well.
Note: Use of heat-conductive grease may interfere with contact
between spring clip and copper well tube.
►Verify control is tightly clamped to well.

Burner will not fire until boiler water has dropped to high

limit differential set-point (10° below high limit setting).
►Verify high temperature setting is correct.

When ECONOMY function is active, control monitors

heating demand and establishes Target boiler temperatures

below high limit setting to conserve fuel. Burner will not

fire until boiler temperature drops to Target Temperature

Differential.

YES

YES

YES

YES

NO

NO

NO

NO