Warning – Dunkirk Q90-200 Series II User Manual

Page 40

Advertising
background image

40

Initial Service Checks

1.

Before Troubleshooting:

A. Verify circuit breaker is on or fuse is OK at electrical

panel.

B. Verify service switch is ON.
C. Verify Gas is ON at:

• Gas meter
• Appropriate manual shutoff valves
• Gas control valve

D. Verify thermostat is calling for heat.
E. Verify wire connections at integrated boiler control

(IBC) and originating control are securely plugged

in or connected.

F. Check hoses are securely connected and are not

plugged or damaged.

2.

Troubleshooting Tools:

A. Voltmeter to verify 120 VAC and 24 VAC
B. Continuity Tester
C. Inclined Manometer or Pressure Gauge with 0-2.0”

range (0.01” scale) for measuring suction pressures

at pressure switch.

D. U-Tube Manometer or Differential Pressure Gauge

with 0-14” range (0.1” scale) for measuring inlet

and manifold gas pressures.

3.

System Status:

A. Consult “System Status” on page 40.
B. See Figure 19, Page 26, for location of boiler

Diagnostic Indicator Lamps.

15 - TROUBLESHOOTING

WARNING

Fire, explosion or shock hazard may cause death or

serious injury. Do not attempt to modify physical or

electrical characteristics of this boiler in any way.

!

• In reset from lockout condition, all electrical meter

readings at gas control valve (24 vac) must be taken

within trial for ignition period.

• If any component dose not function properly, make

sure it is correctly installed and wired before replacing.

• Static electricity discharge can damage integrated

boiler control (IBC). Touch metal surface to discharge

static electricity before touching IBC.

• IBC cannot be repaired. If it malfunctions it must be

replaced.

• Only trained, experienced service technicians should

service IBC systems. Follow troubleshooting to check

out system and sequence of operation for normal light

off sequence.

• Defective control is least likely cause of malfunction.

If you suspect unit has defective control, read through

troubleshooting chart before replacing it.

• It is unlikely two consecutive controls are defective. If

this seems to be the case chances are the controls are

not the cause but rather malfunction is due to some

other problem such as electrical short burning out

transformer.

Advertising