15 - troubleshooting, Troubleshooting chart 4 – Dunkirk Q90-200 Series II User Manual

Page 44

Advertising
background image

44

Troubleshooting Chart 4

IGNITER/SENSOR WARMS

UP AND GLOWS

YELLOW/ORANGE

DURING 20 SECOND

WARM UP

CHART 3

YES

NO

CHECK FOR 120 VAC

BETWEEN TERMINALS 1

AND 2 AT CONNECTOR

CN1 ON IBC (DURING

IGNITER WARM UP)

NO

REPLACE IBC

YES

CHECK FOR 120 VAC AT

IGNITER/SENSOR LEADS

ON WIRING HARNESS

(DURING IGNITER

WARM UP)

NO

REPAIR/REPLACE WIRING

FROM IBC

TO IGNITER/SENSOR

YES

REPLACE IGNITER/SENSOR

AFTER 20 SECOND

IGNITER WARM UP, GAS

VALVE IS ENERGIZED
VALVE LIGHT IS ON

2 SECONDS LATER POWER

IS REMOVED FROM
IGNITER/SENSOR

IGNITER LIGHT IS OFF
DOES MAIN BURNER
LIGHT?

CHECK FOR 24 VAC

ACROSS TERMINALS MV

ON THE GAS CONTROL.

WHILE VALVE/FLAME

INDICATOR LIGHT IS ON

NO

NO

CHECK FOR 24 VAC

ACROSS TERMINALS
CN6-2 AND CN6-5 ON

IBC, WHILE THE VALVE/

FLAME LED IS LIT

NO

REPLACE IBC

YES

REPAIR/REPLACE WIRING

BETWEEN IBC AND

GAS CONTROL

YES

CHECK IF IGNITER/

SENSOR POSITION IS OK?

TIP SHOULD BE SLANTED

TOWARDS BURNER

RESTORE IGNITER/SENSOR

TO CORRECT POSITION.

DO NOT RELOCATE

NO

YES

CHECK GAS SUPPLY
PRESSURE AT INLET

PRESSURE TAPPING ON

GAS CONTROL IS GAS

PRESSURE GREATER

THAN 4.0" W.C.?

NO

ARE ALL MANUAL

SHUT-OFFS IN THE GAS

SUPPLY LINE AND ON

THE GAS CONTROL IN

THE OPEN OR ON

POSITION?

OPEN OR TURN ON ALL

MANUAL SHUTOFFS

NO

YES

CONTACT THE GAS UTILITY

TO TURN THE GAS ON

YES

CHART 5

CHART 5

YES

YES

15 - TROUBLESHOOTING