AVOID THE FOLLOWING

Dead Spots

Corners

Alcoves

Behind doors

Cold Spots

Concealed pipes or ducts

Stairwells - drafts

Unheated rooms on the other side
of the wall

Hot Spots

Concealed pipes

Fireplaces

TVs or radios

Lamps

Direct sunlight

Kitchens

Thermostat Installation

• Follow instructions included with your thermostat.
• Locate thermostat five feet above floor on inside wall.
• Mount directly on wall or vertically mount on outlet box.

Thermostat should sense average room temperature.

• Set heat anticipator at 0.7 amps.
• Connect 24 volt thermostat leads to the two (2) yellow

wires located in service switch junction box, located

on outer jacket of boiler. See Figure 15, Page 22

for

service switch junction box and thermostat field wiring

connections.

Connect Circulator Pump Wiring

NOTICE

Label all wires prior to disconnection when servicing

controls. Wiring errors can cause improper and

dangerous operation. Verify proper operation after

servicing.

See Figure 16, Page 24 and Figure 17, Page 25 for service

switch junction box and circulator pump field wiring

connections. If the two 120 volt circulator wire terminals

inside junction box are not used, leave two wire nuts to

prevent short circuit.

9 - ELECTRICAL WIRING