7 - COMBUSTION AIR AND VENT PIPE

US Installation Requirements

• Venting system shall terminate at least 3 ft. (0.9m)

above any forced (mechanical) air inlet located within

10 ft. (3m) horizontally to any building.

• Venting system shall terminate minimum of 1 ft.

(0.3m) above grade or expected snow level in such a

way that it cannot be blocked by snow.

• Termination shall be not less than 7 ft. (2.1m) above

adjacent public walkway, paved driveway or sidewalk.

• Vent terminal shall not be installed closer than 3 ft.

from inside corner of L shaped structure.

• Venting system shall terminate at least 1 ft. from any

air opening (i.e. window, door, or non-mechanical inlet)

into any building.

• Vent termination should be kept at least 3 ft. away

from vegetation.

• Venting system shall terminate at least 4 ft.

horizontally from, and in no case above or below,

unless 4 ft. (1.22m) horizontal distance is maintained,

from electric meters, gas meters, regulators, and relief

equipment.

• Venting system shall not terminate where hot gases

can cause property damage, personal injury, or

where condensate may cause hazardous frost or ice

accumulations.

NOTICE

Exhaust transition from 2” pipe to 3” pipe must be

made in vertical run. (Transition pieces not included.)

6.

General Installation Requirements:

A. Position termination where vent vapors will not

damage plants/shrubs, air conditioning equipment,

or siding on the house.

B. Position termination so it will not be effected by

wind eddy, air born leaves, snow, or recirculated

flue gases. For high wind location termination tees

are required.

C. Position termination where it will not be subjected

to potential damage by foreign objects, such as

stones, balls, etc.

D. Position termination where vent vapors are not

objectionable.

E. Put vent on wall away from prevailing winter wind.

Locate or guard vent to prevent accidental contact

with people or pets.

F. Avoid locations where snow may drift and block

vent. Ice or snow may cause boiler to shut down if

vent becomes obstructed.

G. Under certain conditions, flue gas will condense,

forming moisture, and may be corrosive. In such

cases, take steps to prevent building materials at

vent from being damaged by exhaust of flue gas.

• Every outside wall penetration shall be permanently

sealed to prevent entry of combustion products into

building.

• Venting that discharges flue gases perpendicular to

the adjacent wall shall be located not less than 10 ft.

(3m) horizontally or must be a minimum of 2 ft. (0.6m)

above or must be a minimum of 25 ft. (7.6m) below

from an operable opening in an adjacent building.

Canadian Installation Requirements

• Venting system shall terminate at least 6 ft. (1.8m)

away from any forced (mechanical) air inlet to any

building.

• Venting system shall terminate a minimum of 1 ft.

(0.3m) above grade or expected snow level such a way

that it cannot be blocked by snow.

• Termination shall be not less than 7 ft. (2.1m) above

adjacent public walkway, paved driveway or sidewalk

• Vent terminal shall not be installed closer than 3 ft.

from inside corner of L shaped structure.

• Vent shall not terminate within 1 ft. (0.3 m) for inputs

up to and including 100,000 Btu/hr (30kW) and 3 ft.

(0.9 m) for inputs exceeding 100,000 Btu/hr (30kW) of

window or door that can be opened in any building, of

any non-mechanical air-supply inlet to any building, or

of combustion air inlet of any other appliance.

• Venting system shall terminate at least 4 ft.

horizontally from, and in no case above or below,

unless 4 ft. (1.22m) horizontal distance is maintained,

from electric meters, gas meters, regulators, and relief

equipment.

• Venting system shall not terminate where hot gases

can cause property damage, personal injury, or

where condensate may cause hazardous frost or ice

accumulations.

• First 3 feet (900mm) of plastic venting must be readily

accessible for visual inspection.**

• Vent shall not terminate underneath veranda, porch or

deck unless,

a. The veranda, porch or deck is fully open on minimum

of two sides beneath floor, and

b. The distance between top of vent termination and the

underside of the veranda, porch or deck is greater

than 1 ft. (0.3 m).