See “Troubleshooting” on page 31 for detailed sequences of

operation and troubleshooting procedures. See separately

provided “Repair Parts Manual” for locations of control

components and accessories described.

Integrated Boiler Control (IBC)

• Integrated Boiler Control (IBC) is a microprocessor

based controller for high efficiency gas boilers.

• Controller monitors all safety controls which control

operation of combustion air blower, circulator pump,

burner, and combination hot surface igniter/flame

sensor.

• Controller is not intended for use with vent damper.

Controller is mounted on control panel inside boiler.

Contains five diagnostic indicator lights.

Gas Control Valve
Electronic 24 volt gas control valve contains 1:1 gas/air

pressure regulator, controls gas flow to main burner of

appliance. Suited for both natural and LP gas, and rated in

accordance with ANSI Z21.21 - latest revision and CGA-

6.5-M95.

Hot Surface Igniter

• 120 volt hot surface igniter heats up 1800°F initiates

combustion of gas in burner.

• Igniter is mounted next to burner through gas/air mixer.
• Igniter also serves as means for proving main burner

flame by flame rectification.

A. In event of lack of flame signal on three consecutive

trials for ignition, IBC will lock out.

B. “Valve” and “Flame” diagnostic indicator lamps blink

indicating failure mode as lack of flame signal.

C. Manually reset IBC from lockout by removing and

re-establishing thermostat’s call for heat, or turn

service switch off, then back on. See Figure 19.

High Limit Control

NOTICE

Maximum set-point of limit control must not exceed

190°F.

• High limit control determines maximum boiler water

temperature and provides means for protecting boiler

and heating system from unsafe operating conditions

which could damage boiler.

• Control is mounted in ½” NPT control well and ¾” x ½”

bushing on top of front boiler section at hot water outlet.

• Control is tied in with IBC and factory set at 190°F water

temperature.

• High limit set-point is field adjustable and may be set

between 100°F and 190°F.

• Field set-point adjustment for each installation depends

on heating system requirements.

• Differentials are automatic, vary based on control

settings and boiler temperature.

• Refer to limit manufacturer instructions provided with

limit control.

Casting Temperature Safety Switch

NOTICE

Never run cold water into hot, empty boiler.

Casting temperature safety switch (230°F set-point) shuts

off boiler by shutting off power to IBC, result of lack or loss

of boiler water. Power indicator light goes out.
Switch is installed on top of aluminum boiler section behind

supply piping.
Fault requires manual reset of casting temperature safety

switch, restarting boiler. Verify boiler is filled with water

before resetting switch.