15 - TROUBLESHOOTING

High Limit Control and LWCO

LED Legend and LWCO Test Button

1

HI TEMP illuminates when boiler water temperature

reaches high limit setting. Remains lit until water

temperature falls 10°F. Limit prevents burner operation

while this LED is on.

2

LWCO ACTIVE Indicates low water cut-off function is

active. When control is installed with Electro-well, LED is

on at all times when control is powered. If the control is

installed with a well other than Electro-well, LED will not

illuminate indicating the control is not providing low water

cutoff functionality.

WARNING

Burn and scald hazard. Do not add water until boiler

has fully cooled. Failure to follow these instructions

could result in death or serious injury.

!

3

LWCO LOW WATER Illuminates if boiler is in low water

condition. Control will prevent burner operation during this

condition.
Important: System must be checked by qualified service

agency prior to resuming operation.

4

ECONOMY ACTIVE Indicates that thermal targeting

function is active and control reduces boiler temperature

to conserve fuel. Economy feature is activated using the

ECONOMY dial.

5

ECONOMY TARGET When feature is active, control

continually sets target temperatures below high limit

setting to maximize fuel efficiency. When boiler reaches

target temperature, LED illuminates and burner shuts

down. Boiler water continues to circulate and het the

house as long as thermostat call continues. LED stays lit

until boiler temperature drops below differential at which

point boiler will be allowed to fire again.
Note: LED illuminates regularly during normal boiler

operation.

6

PURGE Control is purging latent heat from boiler and

will not fire until temperature drops to 135°F.

7

LWCO To Test LWCO: Press and hold TEST button. Red

Low Water light will illuminate and burner circuit will de-

energize.

Figure 21 - LED Legend