Dunkirk Q90-200 Series II User Manual

Page 36

Advertising
background image

36

Inspect Venting & Air Intake System - Operate boiler.

Verify all vent/air intake connections are gas-tight and

water-tight. Repair any leaks immediately.

Inspect Condensate Drain - Verify all connections are

watertight, and condensate flows freely. Repair any leaks

immediately.

Inspect System Piping - Verify all connections are

watertight. Repair any leaks immediately.

Test Ignition System Safety Shutoff

1.

Turn off manual gas shut off valve.

2.

Set thermostat to call for heat.

3.

Boiler begins normal sequence of operation.

4.

After approximately 30 seconds (pre-purge and igniter

warm-up period), lamp D illuminates, indicating gas

valve is powered.

5.

After 4 seconds, gas valve closes, lamp D goes out as

integrated boiler control senses flame is not present.

6.

To restart system, follow operating instructions. See

“Startup” on page 29.

Test And Adjust High Limit Control

• At initial start up, with Economy Feature activated,

control establishes 145°F target temperature.

• While burner is operating, adjust setting on high limit

control below actual boiler water temperature.

• Burner should go off while circulator continues to

operate.

• Raise limit setting above boiler water temperature and

burner should re-ignite after pre-purge and igniter

warm-up period.

• Set high limit control to design temperature

requirements of system.

• Maximum high limit setting is 190°F.
• Minimum high limit setting is 100°F.
• After testing, restore Economy setting. If heating

demand is high, target will increase over time to satisfy

heat load.

• See Manufacturer provided literature for specific

features of high limit control.

Test Other Safety Controls
If boiler is equipped with low water cut off, manual reset

high limit, or additional safety controls, test for operation

as outlined by control manufacturer.
Burner should be operating and should go off when controls

are tested.
When safety controls are restored, burner should re-ignite.

Set Thermostat Heat Anticipator (If Used) And Verify

Thermostat Operation

• Set heat anticipator at 0.7 amps for single thermostat

connected to yellow thermostat lead wires in furnished

field wiring junction box.

• For other wiring configurations, refer to instructions

provided by thermostat manufacturer regarding

adjustment of heat anticipator.

• Cycle boiler with thermostat.
• Raise thermostat to highest setting.
• Verify boiler goes through normal start up cycle.
• Lower thermostat to lowest setting and verify boiler

shuts off.

Measure Natural Gas Input Rate
Correct input rate is essential for proper and efficient

operation of burner and boiler.

1.

Determine elevation at installation site.

2.

See “Boiler Ratings & Capacities” on page 4. to

determine correct approximate input rate for local

elevation.

3.

Obtain yearly average heating value of local gas utility.

At sea level elevation, approximately 1000 BTU per

standard cubic foot.

4.

Operate boiler for 5 minutes.

5.

Turn off all other gas appliances, extinguishing standing

pilots where applicable.

6.

At gas meter, measure time in seconds required to use

one cubic foot of gas.

7.

Calculate “input rate”. Refer to following formula:

Btuh Input Rate = 3600 x Heating Value From Step 3

Time In Seconds From Step

6

8.

Measured input rate should be within +0/-2% of

input rating found in step 2. See “Adjustments And

Checkout” on page 36.

14 - CHECKOUT PROCEDURE & ADJUSTMENTS

Advertising