Dunkirk Q90-200 Series II User Manual

Page 28

Advertising
background image

28

Filling Boiler With Water And Purging Air For Systems

With Conventional Closed Type Expansion Tanks
Refer to diagrams on “Near Boiler Piping” on pages 9 and

10 for more information.

1.

Close all zone service valves on supply and return

piping. Close expansion tank service valve. Drain

expansion tank. Open feed valve and fill boiler with

water. Hold relief valve open until water runs air free

for five seconds to rapidly bleed air from boiler, let

relief valve snap shut.

2.

Open zone service valve on supply pipe for first zone.

Open purge valve on first zone. Feed water will fill

zone, pushing air out purge valve. Close purge valve

when water runs air free. Close zone service valve.

3.

Repeat step 2 for remaining zones.

4.

Open expansion tank service valve and tank

vent. Fill tank to proper level and close tank vent.

Remove handle from expansion tank service valve so

homeowner doesn’t accidentally close it.

5.

Open all service valves. Any air remaining trapped

in return lines between service valves and boiler will

push towards expansion tank when boiler is placed in

operation.

6.

Inspect piping system. Repair any leaks immediately.

11 - STARTUP

Water Treatment And Freeze Protection

Filling Boiler With Water And Purging Air For Systems

With Diaphragm Type Expansion Tanks
Refer to the appropriate diagrams “Near Boiler Piping” on

pages 10 and 11.

1.

Close all zone service valves on supply and return

piping. Open feed valve and fill boiler with water. Verify

air vent is open. Hold relief valve open until water runs

air free for five seconds to rapidly bleed air from boiler,

let relief valve snap shut.

2.

Open zone service valve on supply pipe for first zone.

Open purge valve on first zone. Feed water fills zone,

pushing air out purge valve. Close purge valve when

water runs air free. Close zone service valve.

3.

Repeat step 2 for all remaining zones.

4.

Open all service valves. Any air remaining trapped

in return lines between service valves and boiler

are pushed towards air vent when boiler is placed in

operation.

5.

Inspect piping system. Repair any leaks immediately.

NOTICE

Do not use stop leak compounds or other chemicals

not listed in this manual. Repair leaks in threaded

connections of aluminum boiler sections. Aluminum

threads do not seal themselves.

6.

Systems with automatic fill valves and leaks will cause

excessive fill water. This water contains oxygen.

Excessive oxygen will cause the aluminum boiler to

corrode over time. All system leaks should be repaired

immediately.