DRAFT INDUCER TEMPERATURE SAFETY

SWITCH

Draft inducer runs through 30 second post purge and

switches OFF.

Circulator runs with thermostat on call for heat.

When temperature safety switch contacts connect

before end of call for heat, control goes in normal

light-off sequence.

LOSS OF COMBUSTION AIRFLOW

If combustion airflow is lost while burner is firing

(Differential air pressure switch contacts open) gas

valve is de-energized.

Valve and flame lights go out.

Draft inducer runs through 30 second post purge.

If call for heat remains, IBC waits 5 minutes for airflow

to be re-established.

If airflow does not re-establish control lockout problem

with combustion airflow.

Purge light blinks

.

Control automatically reset after 15 minutes.

LOSS OF FLAME SIGNAL

If established flame signal is lost while control expects

burner is operating, control immediately de-energizes

gas valve.

Valve and flame lights go out.

Draft inducer runs through 30 second post purge.

Control attempts to light boiler 3 times. If flame is not

proven, control lockout problem establishing flame

signal.

Valve light is blinking

.

Control automatically resets after 1 hour.

HIGH LIMIT CONTROL

[REFER TO PAGE 37 FOR MORE INFO]

If boiler water temperature reaches high

limit setpoint, high limit n.c. contacts open

immediately, closing gas valve.

Valve and flame lights go out.

Draft inducer continues to run for 30 second post

purge and switch OFF.

Circulator runs as long as thermostat calls for

heat.

When high limit contacts connect before end of

call for heat - control goes into normal light-off

sequence.

CASTING TEMPERATURE SAFETY SWITCH

If burner operates when boiler has no water,

aluminum boiler sections heat up rapidly.

Casting temperature safety switch contacts will

open, breaking 24 volt power to IBC.

Power indicator light goes out.

Requires manual reset to re-close contacts.

Power light goes out.

CIRCULATOR PUMP

Circulator is energized as long as thermostat calls

for heat during lockout.

Recovery from any lockout requires reset, which

can be accomplished by:

(a) Removing and re-establishing thermostat’s

call for heat or turning service switch off

and back on;

or

(b) Waiting for control to automatically reset after

15 minutes for loss of combustion airflow or one

hour for loss of flame.

12 - DETAILED SEQUENCE OF OPERATION

If draft inducer temperature reaches temperature

safety switch set-point, safety switch contacts open

immediately, closing gas valve

(light goes out)

.