Echelon OpenLNS Commissioning Tool User Manual

Page 257

Advertising
background image

OpenLNS CT User’s Guide

241

OpenLNS CT Drawing

Synchronize Drawing
to Database (fix-up
Drawing)

Updates the OpenLNS CT drawing to be consistent with the
OpenLNS database.

Synchronize Monitor
Sets between
Drawing and
Database

Updates the monitor sets in the OpenLNS CT drawing to be
consistent with the OpenLNS database. A monitor set is a group of
point definitions that OpenLNS CT uses to monitor and control
network variables. If the type or format of a monitored point has
changed, the value displayed will be updated when the point is
monitored with OpenLNS CT.

Update Shapes to
Current OpenLNS
CT Version

Updates SmartShapes to the current version of OpenLNS CT if the
OpenLNS CT drawing was originally created with an earlier version
of OpenLNS CT.

Update Shapes to
Current OpenLNS
CT Language

Updates SmartShape menus to current OpenLNS CT language. For
example, if you open a network with the German version of
OpenLNS CT that was created with the English version, this option
will convert the SmartShape menus to German. All the dialogs are
in the language of the respective version of OpenLNS CT. The
language conversion may take some time; therefore, this option
should not be used frequently.

Reset Visio
Workspaces

Corrects instances in which Visio has added multiple documents and
stencils to the drawing in an OpenLNS CT network. For each
drawing in the network, OpenLNS CT opens the drawing file, closes
all other open drawings, opens the standard set of stencils, and saves
the drawing as a workspace.

This option also automatically upgrades the drawings in the
OpenLNS CT network to the current version of Visio.

4. If you are only validating or repairing the OpenLNS network database, click Finish to begin the

resynchronization process and skip to step 16 in which the Synchronization Status dialog opens.
Otherwise, click Next. The Synchronization Scope dialog box opens.