Echelon OpenLNS Commissioning Tool User Manual

Page 329

Advertising
background image

OpenLNS CT User’s Guide

313

• A value of 1 indicates that the style applies to the

SmartShape’s lines.

• A value of 2 indicates that the value applies to the

SmartShape’s fill.

• A value of 4 indicates that the style applies to the

SmartShape’s text.

You can add values together to specify combinations. For
example, a value of 6 indicates that the style applies to the
SmartShape’s fill and text, but not its lines. By default, the style
applies to all three SmartShape attributes.

PingClass

Specifies the ping interval.

• A value of 0 specifies that the default ping interval is used for

this SmartShape.

• A value of 1 specifies that the 1-minute ping interval be used.
• A value of 2 specifies that the 2-minute ping interval be used.
• A value of 3 specifies that the 15-minute ping interval be

used.

A value of 4 specifies that the Never ping interval be used.

Priority

A value of 1 indicates that priority will be enabled for devices
created from this master SmartShape.

ProgramId

Device program ID. OpenLNS CT uses this value first to find the
device template by name. If not specified, the TmplName value
is used.

RequiresVFB

Specifies whether the device requires a virtual functional block.
• A value of 0 specifies that the device does not require a

virtual functional block.

• A value of 1 specifies that the device requires virtual

functional blocks.

• A value of -1 specifies that OpenLNS CT should determine

this value based on the device’s set of network variables,
configuration properties, and message tags.

The default value is -1.

TmplName

Device template name. This must be specified if XifName is
specified. Be sure to specify a unique device template name for
each unique device interface (XIF) file.

• If OpenLNS CT does not first find a device template based

on the ProgramId value, it uses the value in TmplName to
look up the device template by name. If neither is found,
OpenLNS CT searches for a device interface file based on the
XifName value and the XIF search path. If found, the XIF
file is loaded and used. If it is not found, the OpenLNS CT
user is prompted to enter a device interface file when the
device master SmartShape is dragged to the OpenLNS CT
drawing.

XifName

File name or full path of the device interface (XIF) file. If it is
not specified here, the OpenLNS CT user may be prompted for a
device interface when the device master SmartShape is dragged to
the to the OpenLNS CT drawing, depending on the ProgramId

Advertising