Echelon OpenLNS Commissioning Tool User Manual

Page 328

Advertising
background image

312

Creating and Using Custom OpenLNS CT Shapes and Stencils

NewAdvPropCap

Specifies handling of the advanced properties dialog in the new
device wizard.
• A value of 0 specifies that the advanced properties dialog is

not to be displayed.

• A value of 1 indicates that the advanced properties dialog is

to be displayed, but cannot be modified.

• A value of 2 indicates that the advanced properties dialog is

displayed and changes can be made.

• The default value is 0 (the advanced properties dialog is not

displayed).

NewPropCap

Specifies handling of the basic properties dialog in the new device
wizard.
• A value of 0 specifies that the basic properties dialog is not to

be displayed.

• A value of 1 indicates that the basic properties dialog is to be

displayed, but cannot be modified.

• A value of 2 indicates that the basic properties dialog is

displayed and changes can be made.

• The default value is 2 (the basic properties dialog is displayed

and changes are allowed).

NonGrpRcvTimer

Specifies the default non-group receive timer; a value of -1
indicates that the OpenLNS Server default value will be used.
Otherwise, the value is encoded as follows:

Encoded

Value

Seconds

0

0.016

1

0.024

2

0.032

3

0.048

4

0.064

5

0.096

6

0.128

7

0.192

8

0.256

9

0.384

10 0.512
11 0.768
12 1.024
13 1.536
14 2.048
15 3.072

NxeName

Specifies the file name or full path of the application file. If it is
not specified here, the OpenLNS CT user will be prompted for an
application file when a request is made to load the application
image.

ObjStateStyle

Specifies whether the coloring style is applied to the
SmartShape’s fill, line, text, or a combination of the three.