Service pin options – Echelon OpenLNS Commissioning Tool User Manual

Page 357

Advertising
background image

OpenLNS CT User’s Guide

341

Service Pin Options

You can set options for using the service pin when commissioning a device.

Show Service Pin
Data

Displays the service pin data received by OpenLNS CT when you
press the device’s service pin. This option is cleared by default.

You can change this option when you commission a device or router
in the Commission Device/Router Wizard.

Scope: Current network, current OpenLNS CT computer

Serialize Service
Pin Access

Limits service pin installation to only one installer looking for a
service pin message at a time. This option is selected by default.

Clear this check box if multiple users are commissioning devices at
the same time and are working on different channels connected by
configured routers.

Select this check box if multiple users are commissioning devices at
the same time and are working on channels connected by logical
repeaters, or if multiple users are installing devices on the same
channel.

Either setting can be used if you have a single user commissioning
devices at a time on the network.

Scope: Current network, all OpenLNS CT computers

Filter Based on
Channel

Ignores service pin messages not originating from the same channel
on which the device being installed is located. This option is cleared
by default.

Select this check box if the network does not contain any logical
repeaters.

Clear this check box if the network includes any logical repeaters.

Advertising