Checking commlink network loop – cv-ex, Diagram, Overview – Auto-Zone Control Systems Auto-Zone CV & CV-EX Systems Installation & Operation (Version 01C) User Manual

Page 101: Measurements, Action

Advertising
background image

Auto-Zone CV & CV-EX

Section 4

Start-Up and Troubleshooting

4-23

Checking CommLink Network Loop – CV-EX

Diagram

MODEM

RS-232

Serial #

COMPUTER

USB

10/100

ETHERNET

DIAG

24V

T G R

GN

D

485 LOOP POWER

ACT

LNK

USB

C

onf

ig

No

rm

al

To

Zone Manager

Network Loop

The CommLink IV Must Be

Powered Up For These Tests

Set Your Meter

To Read DC Volts

+

-

+

-

+

-

+

-

To 24 VAC

Power Supply

T-To-G

+2.0 VDC

To

+4.0 VDC

R-To-G

+2.0 VDC

To

+4.0 VDC

CommLink IV

Overview

This test checks for proper Network Loop voltages at the CommLink IV.
Tip: The Loop LED (located on the front panel) should “flicker” when the CommLink IV

is attempting to communicate. The Loop LED will flicker more noticeably for a few
seconds when first powered up. If the Loop LED does not flicker, the unit is defective.

Proper loop voltages are essential for reliable communications. It is normal to see fluctua-
tions at this point on the CommLink IV. The average value should be close to the accept-
able range described below. Values will vary upon initial powerup for about 10-15 sec-
onds as the unit attempts to communicate.

Measurements

Network Loop

Acceptable Range

T - G (SHLD)

2.0 - 4.0 Volts DC

R - G (SHLD)

2.0 - 4.0 Volts DC

Action

Condition

Action

If voltages are too high or too low
on either side.

1. Unplug the Network Loop from the CommLink

IV and check for proper loop voltages. If a prob-
lem exists, disconnect each MiniLink Network
Loop until the problem is isolated.

2. Check the CommLink IV Driver chip. Replace

the CommLink IV. The driver chip is not field-
replaceable.

Advertising