Section 2

Auto-Zone CV & CV-EX

2-14

Installation and Wiring

Supply Air Temperature Sensor

The Supply Air Temperature Sensor should be located as close to the rooftop unit
discharge as possible for the best response. Locate the sensor in the center of the widest
part of the duct. Use the supplied template and a 5/16" drill to make a hole for the sensor.
Install the gasket over the probe and mount securely to the duct using the supplied sheet
metal screws. Be sure the gasket is compressed to provide an air-tight seal. For best
accuracy, apply insulation on the outside of the duct, over the sensor. This will help
prevent thermal gradients from affecting the sensor.

Figure 2-10:

Supply Air Temperature Sensor Installation

Mounting Plate

Gasket

Adhesive Backed Drill Guide
Mounting Template

11-1/2" (OE231)

5-1/2" (OE230)

Mounting Plate

4.0"

3/4"

1/4" Hex Head Sheet Metal Screws

Thread
Together

Duct Work

Drill 5/16" Hole In Ductwork For Probe

Leads Are Non-polarized.
Butt Splice Leads To 24 Gauge
Wire Minimum. Connect Leads
To "Analog In" And "Ground"
At Controller.