Minilink interface wiring, Figure 2-19: minilink interface wiring – Auto-Zone Control Systems Auto-Zone CV & CV-EX Systems Installation & Operation (Version 01C) User Manual

Page 37

Advertising
background image

Auto-Zone CV & CV-EX

Section

2

Installation and Wiring

2-25

MiniLink Interface Wiring


All MiniLinks on the CV-EX system must be wired to each other with a Network
communications loop, daisy-chaining the Network loop terminals together. One end of
the CV-EX system Network loop must be connected to the CommLink IV interface. Each
MiniLink on the CV-EX system is then wired from its Local loop terminals to the CV
Controllers on that Local loop. The MiniLink also requires 24 VAC power to operate.
Each MiniLink must be addressed from 1 to 4 with a unique address. The addresses are
set with the address switch at each MiniLink board. See Figure 2-18 for the address
switch location. See Figure 2-19 for wiring information.

R

SH

T

R

SH

T

R

SH

T

R

SH

T

All Communication Loop

Wiring Is Straight Through

Required VA For Transformer

MiniLink = 10VA Max.

See Note 1.

LO
O

P

24VAC

GND

T
SH
R

32

16

8

4

1

2

OFF >

Local Loop

RS-485

9600 Baud

(See Note 3).

Connect To CV

Controller or

System Manager

On Local Loop

Connect To Next

MiniLink And/Or

CommLink On

Network Loop

Network Loop

RS-485

19200 Baud

(See Note 3).

Line Voltage

24VAC

GND

MiniLink Communications Interface

ADD

NETWORK

SH

T

R

Notes:

1.)24 VAC Must Be Connected So

That All Ground Wires Remain

Common.

2.)All Wiring To Be In Accordance

With Local And National Electrical

Codes And Specifications.

3.) All Communication Wiring To Be

2 Conductor Twisted Pair With

Shield. Use Belden #82760 Or

Equivalent.


Figure 2-19:

MiniLink Interface Wiring








Advertising