CV-EX System

See Figure 4-2. The CV-EX system has two types of communications loops. The loops
which the CV controllers are connected to are called the Local Loops. The MiniLink is
always the loop master on the CV-EX local loop
. You must be sure the MiniLink is
connected, powered up, and functioning if you are troubleshooting a Local communica-
tions loop. The other type of loop on the CV-EX system is called the Network Loop. This
loop connects all the MiniLinks together and then ties into the CommLink IV which is
the Network Loop Master.
The CommLink IV jumper switch must be set for multiple
loop operation when used with the CV-EX system. See Figure 4-4 for the correct jumper
switch setting.

Computer

(Optional)

End Of Local Loop

MiniLink

RS-485

9600 Baud

RS-485

19200 Baud

Local Loop

Network Loop Start

Network Loop

Connect To

Network Loop

Connection On

Next MiniLink

Local Loop Start

CV Controller

CV Controller

CV Controller

CV Controller

CV Controller

CV Controller

System Manager

The Comm Loop

Routing Does Not

Have To Follow

The Board Address Sequence

The System Manager Can Be

Connected Anywhere

On The Local Loop

Optional IP Module

Installs Into CommLink IV And

Provides LAN And Internet

Communications

With The Control System

Ethernet Router

(By Others)

When IP Module

Option Is Used

Optional Remote Link II

Connects to CommLink IV And

Provides Alarm Call-Outs. A Second

Remote Link Is Required If Connection To

Job Site Is Desired From Remote Computer.

Phone Cable To Telephone

Wall Outlet Jack

Serial Cable To Remote Link

Ethernet Cable To Router

USB Cable To Computer

All Components Shown Inside This Box Are Optional

CommLink IV

The CommLink IV Is Required For

All Systems. The IP Module,

Remote Link II, And Computer Are

Optional On All Systems. All

Computers Require Installation of

Prism Graphical User Interface

Software

Figure 4-2:

CV-EX System Communications Wiring

Advertising