Troubleshooting, General communications – Auto-Zone Control Systems Auto-Zone CV & CV-EX Systems Installation & Operation (Version 01C) User Manual

Page 96

Advertising
background image

Section 4

Auto-Zone CV & CV-EX

4-18

Start-Up and Troubleshooting

Troubleshooting

The following is a guide to assist in troubleshooting the CV and CV-EX systems. It is
provided as a systematic approach to determining and resolving common system
problems.

General Communications

No CV Units are communicating

Is the CommLink connected and plugged in?
For the CV System, is the CommLink jumper set for single loop operation? See

Figure 4-4.

For the CV-EX System, is the CommLink jumper set for multiple loop operation?

See Figure 4-4.

Are Comm Loop voltages correct? See the Comm Loop troubleshooting section.
Is the Comm Loop open or shorted?
Are the CV Controller address switches set correctly? See Figure 4-8.
Are the CV Controllers powered? Check 24 VAC to the controllers. The PWR

LED should be lit.

Is the Communications Loop shorted? Check Comm Loop voltages.
Is the System Manager connected to the Communications Loop?

Some CV Units are communicating, but others are not

Are the CV Controller address switches set correctly? See the addressing chart

(Figure 4-8.)

Are the CV Controllers powered? Check 24 VAC to the controllers. The PWR

LED should be lit.

Is the COMM LED on the missing CV Controller “flickering”? See Figure 4-7

for location of the COMM LED.

Is the LED2 on the CV Controller blinking an error code? See the Blink Code

chart on the next page.

Are Comm Loop voltages correct at the missing unit? See the Comm Loop

troubleshooting section.