Blink codes – Auto-Zone Control Systems Auto-Zone CV & CV-EX Systems Installation & Operation (Version 01C) User Manual

Page 97

Advertising
background image

Auto-Zone CV & CV-EX

Section 4

Start-Up and Troubleshooting

4-19

Blink Codes

The CV Controller uses LED2 to indicate various diagnostic conditions during powerup
and operation. Starting with power up, the LED blink codes are as follows:

• Off for five seconds

• LED2 blinks the board address (Address 14 = 14 blinks)

• Five second pause

• Twenty second time delay – LED2 blinks twenty times

• Status code is repeatedly blinked every ten seconds to indicate controller

status:

Priority

No. of Blinks

Status

Lowest 1

Normal

Operation

- 2

Override

Active

-

3

Bad Zone Sensor

N/A

4

Not Used for this System

Highest 5

Communication

Failure

Table 4-1:

Diagnostic LED Blink Codes


Only the highest priority failure code will be shown. You must correct the highest priority
alarm before other problems will be indicated.