Checking the minilink network loop – cv-ex, Diagram meter set to read dc volts, Overview – Auto-Zone Control Systems Auto-Zone CV & CV-EX Systems Installation & Operation (Version 01C) User Manual

Page 104: Measurements, Action

Advertising
background image

Section 4

Auto-Zone CV & CV-EX

4-26

Start-Up and Troubleshooting

Checking the MiniLink Network Loop – CV-EX

Diagram

Meter Set To Read DC Volts

+

-

+

-

+ . VDC

to

+4.0 VDC

R - to - G

T - to - G

+

-

+

-

To Other MiniLinks

Or CommLink

On The Network Loop

To Other MiniLinks

Or CommLink

On The Network Loop

MiniLink

MiniLink

To CV Controllers

And System Manager

On Local Loop

To CV Controllers

And System Manager

On Local Loop

2 0

+ . VDC

to

+4.0 VDC

2 0

The indicated readings are typical of a normally operating system. Actual readings may
vary slightly due to the number of units installed and other factors. Any significant
deviation from these values generally indicates a problem.

Note: These tests assume that the CommLink is connected and powered, and that all

MiniLinks, which are connected, are also powered.

Overview

Proper loop voltages are essential for reliable communications. It is normal to see fluctua-
tions on an operating communications loop. The average value should be close to the
acceptable range described below. Values will vary upon initial powerup for about 15-30
seconds as normal communications occur
.

Measurements

Local Loop

Acceptable Range

T - G (SHLD)

2.0 - 4.0 Volts DC

R - G (SHLD)

2.0 - 4.0 Volts DC

Action

Condition Action

Readings near Zero Volts.

Check for shorted wiring.

If voltages are too high or too
low on either side.

1. One or more devices connected to this loop may

have damaged comm driver chips. Replace the
driver chip. See Figure 4-10 & 4-11.

2. Wiring errors. Check for multiple loops inadver-

tently “cross connected”, short circuits, etc.

Advertising