Minilink interface, Auto-zone cv & cv-ex 2-24 installation and wiring, Figure 2-18: minilink interface overview – Auto-Zone Control Systems Auto-Zone CV & CV-EX Systems Installation & Operation (Version 01C) User Manual

Page 36

Advertising
background image

Section 2

Auto-Zone CV & CV-EX

2-24

Installation and Wiring

MiniLink Interface

The MiniLink Interface is only required and used with the CV-EX system. It is not
required for the CV system. It functions as the loop master for each CV-EX system local
loop. With the CV-EX system, each local loop of CV controllers (maximum of 30) is
connected to a MiniLink. Two MiniLinks are supplied with the standard CV-EX system.
This allows up to 60 CV controllers (30 maximum per local loop) to be tied together to
form an integrated system. A CV-EX expansion kit is available which provides another
MiniLink to allow an additional 30 CV controllers to be connected to the system. A
maximum of two expansion kits can be used on the CV-EX system to provide integration
of up to 120 CV controllers. See Figure 2-18 for an overview of the MiniLink.

24 VAC

Power

Network Loop

Communications

Driver Chip

Network Loop

Communications

LED

Local Loop

Communications

LED

Local Loop

Communications

Driver Chip

Address Switch

( Each Board Must Be Addressed Uniquely )

( 1,2,3,4)

Switch Shown Set For Address 1

Local Loop

Connector

Network Loop

Connector

7.50”

4.

50

"

LO
O

P

24VAC

GND

T
SH
R

32

16

8

4

1

2

OFF >

ADD

NETWORK

SH

T

R

Figure 2-18:

MiniLink Interface Overview