Section 4

Auto-Zone CV & CV-EX

4-10

Start-Up and Troubleshooting

CV and CV-EX System

Communications Checklist

CV & CV-EX Systems

CV Units on each loop are correctly addressed from 1 to 30
Power has been cycled after changing addresses
There are no duplicate addresses on the loop
CommLink is connected to the communications loop
All CV Controllers are connected to the communication loop
System Manager is connected to the communications loop
All communication wiring is landed correctly, T to T, R to R, and SHLD to SHLD
CommLink is set for single loop operation (on CV System)
CommLink is set for multiple loop operation (on CV-EX System)
CV Controllers are wired to 24 Volt AC power supply
CommLink is wired to 24 Volt AC power supply
All 24 VAC power wiring is landed correctly—24VAC to 24VAC and GND to GND
CommLink is powered up
CV Units are powered up
System Manager is powered up

Additional Checks for the CV-EX System

MiniLinks are correctly addressed from 1 to 4
MiniLink Power has been cycled after changing addresses
There are no duplicate addresses on the loop
All CV Controllers are connected to a Local communications loop
CommLink is connected to the Network communications loop only
System Manager is connected to one of the Local communications loops

Optional Equipment

Personal computer is correctly connected to the CommLink
Prism™ software installed on personal computer
Remote Link II is correctly connected to the CommLink
Remote Link II connected to a working phone line
IP Module is correctly installed in the CommLink
IP Module’s Ethernet cable is connected to router