Auto-Zone CV & CV-EX

Section

2

Installation and Wiring

2-19

CommLink IV DIP Switch Setting


DIP Switch 1 & 2 Off =

Multiple Loop Communications

Required Setting For Auto-Zone CV-EX System

CommLink IV Communication Settings

The SW1 DIP Switch Located On The Circuit Board Inside

The CommLink IV Housing Must Be Set Correctly For

Your Specific Application In Order To Function Properly.

To Check And/Or Set The SW1 Dip Switch, First Remove

The (2) Enclosure Screws That Hold The Top And Bottom

Of The CommLink IV Enclosure Together. Remove The

Top Half Of The Enclosure To Access The Circuit Board

And Dip Switches.

The

DIP Switch Setting Should Be Set To “Multiple”

For The Auto-Zone

System

The CommLink IV Is Factory Set For Multiple Loop

Applications.

SW1

CV-EX

.

Replace The CommLink IV Cover And Secure The

Enclosure Halves Back Together With The (2) Enclosure

Screws That Were Previously Removed.

ALTERA
EPM3032

WattMaster Controls Inc.
COMMLINK IV
YS102074
REV6

MADE IN USA

Figure 2-13:

CommLink IV DIP Switch Setting