CV Controller Inputs & Outputs

24 VAC Power Connector

This connector provides power to the CV Controller.

24VAC - The “hot” side of the control transformer.

GND - The grounded side of the control transformer. If the secondary of the con-
trol transformer is not grounded, you must still observe polarity if the trans-
former powers any other device!

Warning:

Connect only the GND terminal to the grounded side of a transformer.
Failure to properly observe polarity will result in
damage to the system.
Observe polarity at all points in the system.

Analog Input Descriptions

Input #1 - Space temperature is read on this input. If the room sensor with override is
installed, the input is also monitored for push-button override commands. The push-
button is only active during unoccupied hours, so a push during occupied hours has no
effect.

Input #2 - This input is only used if a space temperature sensor that has the slide adjust
option is installed. The slide adjust can be used to offset the current heating and cooling
setpoints.

Input #3 - Supply air temperature is read on this input. The supply air reading is used to
detect equipment failure. Once a heating or cooling stage has activated, the supply air has
thirty minutes to change by 5

°F or the controller assumes a mechanical failure has

occurred. The supply air also prevents cooling stages from activating if the temperature is
45

°F or lower in the cooling mode and prevents heating stages from activating if the

temperature is 140

°F or higher in the heating mode.

Input #4 - Outdoor air temperature is read on this input. If you have more than one CV
controller installed on the RS-485 communication loop, only one controller needs this
sensor. The unit that has this sensor will automatically broadcast the outdoor air tempera-
ture to all other controllers on the loop.

Input #5 - This input can be used to monitor an alarm contact closure. If the contact is
closed, the alarm is active.