Auto-Zone CV & CV-EX

Section 3

Programming

3-19

Setpoint Screen #8













Setpoint Screen #9





CVAHU Setpoints

Fan Mode.: Constant

Economizer: Enabled

Use Left/Right Arrow

Line 2 - The CVAHU can operate the fan in one of two

modes:

Continuous or Constant running during
occupied hours.

Cycle with heating or cooling during occupied
hours.

The fan always cycles with heating or cooling
during unoccupied hours. The Left/Right Arrow
keys will toggle the current setting to the opposite
mode.

Line 3 - The CVAHU has the ability to control the

Economizer operation. If you require this feature,
select Enabled; otherwise, select Disabled.

Constant Volume Unit

Uses Schedule #: 0

0 = Internal Clock

1-8 = External Clock

The CVAHU normally uses its own Real Time Clock and an
Internal Week Schedule to determine the Occupied/
Unoccupied mode of operation. The CVAHU does have the
ability to use a Global Broadcast from another scheduling
device on the communications loop if a different schedule is
required. If an external schedule is used, the range of schedule
numbers is one to eight.