Section 2

Auto-Zone CV & CV-EX

2-18

Installation and Wiring

CommLink IV Wiring

24 VAC Power

If Desired A 24 VAC Transformer

Rated At 12 VA Minimum May Be

Used Instead Of The Supplied Power Pack.

Use 18 Gauge Minimum 2 Conductor Wire

Between The Transformer & CommLink IV

Terminals.

(Not

Included)

120 to 24 VAC Power Pack

(Included) Connect To 120/1/60 Duplex

Receptacle (By Others)

USB Cable (Included). Connect

This Cable To Your Computer USB

Port For Directly Connecting To

CommLink IV. Also Used For

Advanced Configuration of

CommLink IV.

CommLink IV

Communications Interface

Notes:

1) Use 18-Gauge Minimum, 2-Conductor Twisted Pair With Shield Cable Belden #82760 Or Equivalent

(Not Included) To Connect The CommLink IV To The MiniLink On Network Loop Or Controller Or System Manager On Local Loop.

2) For Direct Connection Via USB, Your Computer Must Have An Unused USB Port Available. Drivers

For Your USB Port Are Provided On A CD Supplied With The CommLink IV And Will Need To Be

Installed On Your Computer In Order For It To Function Correctly. Please Refer to the CommLink IV

Installation Technical Guide Form: WM-CLIV-TGD Which Is Supplied With The CommLink IV.

3) The CommLink IV Cannot Communicate With The Control System Through Its Ethernet Port And

USB Port At The Same Time.

4) All Wiring Must Conform To Applicable Federal, State & Local Electrical Wiring Codes.

18-Gauge, 2-Conductor

With Shield (Not Included)

Connect To The Controller Or System

Manager On Local Loop Or MiniLink

On Network Loop. See Note 1.

MODEM

RS-232

Serial #

COMPUTER

USB

10/100

ETHERNET

DIAG

24V

T G R

GN

D

485 LOOP POWER

ACT

LNK

USB

C

onf

ig

No

rm

al

Optional - Prefabricated Ft. Long CAT5

Ethernet Cable (Included With Optional OE415-

02 IP Module Kit).

If A Longer

Ethernet Cable Is Required, You Will Need To

Obtain (From Others) And Install An Ethernet

Cable Of The Required Length For Your

Installation.

10

Connect To A 10/100 Base-T

Ethernet Router On Your LAN.

When An Optional Remote

Link Is Used, Connect This

Cable To CommLink IV And

Remote Link As Shown. Cable

Is Included With Remote Link.

Molded Modem Cable.

Part #HZ000098

Supplied With RemoteLink II

9P
in

Fem

ale

25 Pin

Male

WARNING!

If You Are Using The IP Module

With Your CommLink, Do Not Have Your

Ethernet Connection And USB Connection

Connected At The Same Time. This Could

Cause Unreliable Communications.

Optional Items Not

Required For

CommLink Only

Installations.

USB Switch

Should Be Set

To Normal

Figure 2-12:

CommLink IV Interface Wiring