Communications loops, Checking commlink local loop – cv, Diagram – Auto-Zone Control Systems Auto-Zone CV & CV-EX Systems Installation & Operation (Version 01C) User Manual

Page 98: Overview, Measurements, Action, If voltages are too high or too low on either side, Network loop acceptable range, Condition action

Advertising
background image

Section 4

Auto-Zone CV & CV-EX

4-20

Start-Up and Troubleshooting

Communications Loops

Checking CommLink Local Loop – CV

Diagram

MODEM

RS-232

Serial #

COMPUTER

USB

10/100

ETHERNET

DIAG

24

V

T G R

GN

D

485 LOOP POWER

ACT

LNK

USB

C

onfi

g

No

rm

al

To

Zone Manager

Network Loop

The CommLink IV Must Be

Powered Up For These Tests

Set Your Meter

To Read DC Volts

+

-

+

-

+

-

+

-

To 24 VAC

Power Supply

T-To-G

+2.0 VDC

To

+4.0 VDC

R-To-G

+2.0 VDC

To

+4.0 VDC

CommLink IV

Overview

This test checks for proper loop voltages at the CommLink IV.
Tip: The Loop LED (located on the front panel) should “flicker” when the CommLink IV

is attempting to communicate. The Loop LED will flicker more noticeably for a few
seconds when first powered up. If the Loop LED does not flicker, the unit is defective.

Proper loop voltages are essential for reliable communications. It is normal to see fluctua-
tions at this point on the CommLink IV. The average value should be close to the accept-
able range described below. Values will vary upon initial powerup for about 10-15 sec-
onds as the unit attempts to communicate.

Measurements

Network Loop

Acceptable Range

T - G (SHLD)

2.0 - 4.0 Volts DC

R - G (SHLD)

2.0 - 4.0 Volts DC

Action

Condition Action

If voltages are too high or too
low on either side.




1. Unplug the Comm loop from the CommLink IV and

Check for proper loop voltages. If a problem exists,
disconnect each CV Unit from the loop until the
problem is isolated.

2. Replace the CommLink IV. The driver chip is not

field-replaceable. See Page 4-22.

Advertising