Checking the minilink local loop – cv-ex, Diagram meter set to read dc volts, Overview – Auto-Zone Control Systems Auto-Zone CV & CV-EX Systems Installation & Operation (Version 01C) User Manual

Page 106: Measurements, Action

Advertising
background image

Section 4

Auto-Zone CV & CV-EX

4-28

Start-Up and Troubleshooting

Checking the MiniLink Local Loop – CV-EX

Diagram

Meter Set To Read DC Volts

NETWORK

LOOP

G

T

R

G

T

R

+

-

+

-

+1.9 VDC

to

+2.1 VDC

R - to - G

T - to - G

NETWORK

LOOP

G

T

R

G

T

R

+

-

+

-

+2.9 VDC

to

+3.1 VDC

To Other MiniLinks
Or CommLink
On The Network Loop

To Other MiniLinks
Or CommLink
On The Network Loop

MiniLink

MiniLink

To CV Controllers
And System Manager
On Local Loop

To CV Controllers
And System Manager
On Local Loop

The indicated readings are typical of a normally operating system. Actual readings may vary
slightly due to the number of units installed and other factors. Any significant deviation
from these values generally indicates a problem.

Note: These tests assume that the MiniLink being checked is powered up.

Overview

Proper loop voltages are essential for reliable communications. It is normal to see fluctua-
tions on an operating communications loop. The average value should be close to the
acceptable range described below. Values will vary upon initial powerup for about 30-45
seconds. Voltages fluctuate as normal communications occur.

Measurements

Local Loop

Acceptable Range

T - SHLD

2.9 - 3.1 Volts DC

R - SHLD

1.9 - 2.1 Volts DC

Action

Condition Action

Readings near zero volts.

Check for shorted wiring.

If voltages are too high or too low
on either side.

1. One or more devices connected to this loop may

have damaged Comm Driver chips. Replace the
driver chip.
See Figure 4-10 & 4-11.

2. Wiring errors. Check for multiple loops inadver-

tently “cross connected”, short circuits etc.

Advertising