background image

Auto-Zone CV & CV-EX

Section 3

Programming

3-5

View Alarms Screen

Alarm Address Locations










Alarm Clearing



SYSTEM ALARM STATUS

Alarm @ Unit ID 118

The System Manager can be programmed to poll all Auto-Zone
units on your system for alarm information. This allows the
centrally located System Manager to display an Alarm Indicator
whenever an alarm condition exists anywhere on your system.
The actual alarms are not displayed on this screen; only the
Unit ID where the alarm is located is displayed. The example
shows that a unit at location 118 has experienced an alarm
condition. This alarm may or may not be current, as the System
Manager latches the alarm condition. This makes it possible to
determine if any intermittent alarm conditions have occured. If
you have Level 2 access, you can enter the full system access
mode, select that unit for display, and determine the exact
alarm condition for that unit. The alarm conditions are always
displayed on the Status Screens.

SYSTEM ALARM STATUS

Clear Alarms? YES

To Change Response

Use Left/Right Arrow

If all the alarm conditions have been corrected at the individual
units, you can clear these alarms from the System Manager on
the following screen. Use the Left/Right arrow keys to select
the YES/NO response desired. If you clear the alarms, but
some still exist, the System Manager will show an alarm
indication when the affected unit is polled again.

Advertising