Checking the minilink network driver – cv-ex, Diagram meter set to read dc volts, Overview – Auto-Zone Control Systems Auto-Zone CV & CV-EX Systems Installation & Operation (Version 01C) User Manual

Page 105: Measurements, Action

Advertising
background image

Auto-Zone CV & CV-EX

Section 4

Start-Up and Troubleshooting

4-27

Checking the MiniLink Network Driver – CV-EX

Diagram

Meter Set To Read DC Volts

+

-

+

-

+2.4 VDC

to

+3.3 VDC

R - to - G

T - to - G

+

-

+

-

+2.4 VDC

to

+3.3 VDC

To Other MiniLinks

Or CommLink

On The Network Loop

To Other MiniLinks

Or CommLink

On The Network Loop

MiniLink

MiniLink

To CV Controllers

And System Manager

On Local Loop

To CV Controllers

And System Manager

On Local Loop

Note: These tests assume that the MiniLink being checked is powered up.

Overview

This check is intended to determine if the Network Comm Driver chip on a MiniLink is
damaged.
Tip: Before unplugging the Network loop from the MiniLink, observe the Network Loop

LED (located near the connector). It should periodically “flicker” as the CommLink
requests data from the MiniLink. The LED will also flicker when power to the
CommLink is cycled. If the LED is not flickering, the unit is not communicating with
the CommLink.

Damage typically occurs when the communications loop is exposed to excessive voltage, as
may occur during installation due to wiring errors. The driver chips are socketed on all
boards to facilitate servicing. It is unusual for driver chips to fail during normal operation.
Almost all failures occur as a result of wiring related problems.

Measurements

Network Loop

Acceptable Range

T - SHLD

2.4 - 3.3 Volts DC

R - SHLD

2.4 - 3.3 Volts DC

Note: .Minor variances may not indicate a problem if both tests indicate similar values.

Action

Condition Action

If voltages are too high or too
low on either side.

The MiniLink has a damaged Network Comm Driver
chip. Replace the driver chip. See Figure 4-10 & 4-11.