Section 4

Auto-Zone CV & CV-EX

4-6

Start-Up and Troubleshooting

MiniLink


The MiniLink communications interface is only required when you are installing a CV-
EX system. It is not required for the CV system. Its address switch must be set correctly,
it must be correctly wired into the system, and it must be powered up in order for the CV-
EX system to operate correctly. The address switches must be set and the power cycled in
order for the address to be recognized by the system. See Figure 4-5 for MiniLink wiring
and addressing.

Notes:

16

32

8

4

2

1

Caution!

The MiniLinks Must Have Address Switches Set Between 1

And 4 (Up To 4 MiniLinks Are Allowed Per CV-EX System).

The MiniLinks Should Be Addressed In Consecutive Order

Starting With Address #1. Address #1 Must Be Present On

The Loop For The System To Function.

Address Switch Shown Is

Set For Address 1

Address Switch Shown Is

Set For Address 4

MiniLink

Address Switch

These Switches Must Be

In The OFF Position

As Shown

Note:
The Power To The MiniLink Must Be Removed And

Reconnected After Changing The Address Switch.

Caution:
Disconnect All Communication Loop Wiring

From The MiniLink Before Removing Power
From The MiniLink. Reconnect Power And Then

Reconnect Communication Loop Wiring.

ADD

The Address For Each MiniLink

Must Be Unique To The Other MiniLinks

On The Network Loop. Loop #1 MiniLink

Should Be Addressed As #1

Loop #2 MiniLink Should Be Addressed

As #2 Etc.

1.) 24 VAC Must Be Connected So

That All Ground Wires Remain

Common.

2.) All Wiring To Be In Accordance

With Local And National Electrical

Codes And Specifications.

3.) All Communication Wiring To Be

2 Conductor Twisted Pair With

Shield. Use Belden #82760 Or

Equivalent.

R

SH

T

R

SH

T

R

SH

T

R

SH

T

All Communication Loop

Wiring Is Straight Through

Required VA For Transformer

MiniLink = 10VA Max.

See Note 1.

LO
OP

24VAC

GND

T
SH
R

32

16

8

4

1

2

OFF >

Local Loop

RS-485

9600 Baud

(See Note 3).

Connect To CV

Controller or

System Manager

On Local Loop

Connect To Next

MiniLink And/Or

CommLink On

Network Loop

Network Loop

RS-485

19200 Baud

(See Note 3).

Line Voltage

24VAC

GND

MiniLink Communications Interface

ADD

NETWORK

SH

T

R

Figure 4-5:

MiniLink Wiring and Addressing