calculated value to the actual value it received in the CRC filed.

5.3.3 Exception Response

If an error occurs, the slave sends an exception response message to master
consisting of the slave address, function code, exception response code and error

check field. In an exception response, the slave sets the high-order bit (MSB) of the

response function code to one. The exception response codes are listed below.

Code

Name

Descriptions

01

Illegal Function

The message function received is not allowable
action.

02

Illegal Data Address

The address referenced in the data field is not valid.

03

Illegal Data Value

The value referenced at the addressed device
location is no within range.

04

Slave Device Failure

An unrecoverable error occurred while the slave was

attempting to perform the requested action.

05

Acknowledge

The slave has accepted the request and processing
it, but a long duration of time will be required to do
so.

06

Slave Device Busy

The slave is engaged in processing a long-duration
program command.

07

Negative Acknowledge

The slave cannot perform the program function

received in the query.

08

Memory Parity Error

The slave attempted to read extended memory, but
detected a parity error in the memory.



5.3.4 Modbus TCP/IP register table
The Managed Switch start support Modbus TCP/IP client service for the Factory
automation applications.

The command of Modbus only supports in the command line interface- console and

telnet mode that allows user to modify some parameters like as idle time, number of

Modbus master and Modbus service port.

Word Address

Data Type

Description

System Information

0x0000

16 words

Vender Name = “Westermo”
Word 0 Hi byte = ‘K’
Word 0 Lo byte = ‘o’
Word 1 Hi byte = ‘r’
Word 1 Lo byte = ‘e’
Word 2 Hi byte = ‘n’
Word 2 Lo byte = ‘I’