Westermo MDI-112-F4G User Manual

Page 173

Advertising
background image

169

0x33BF
0x33C0 to
0x33DF

Ring 30’s Information

0x33E0 to
0x33FF

Ring 31’s Information

Note: the Modbus TCP/IP client will return 0xFFFF to Modbus master when pulling

reserved address.


5.3.5 CLI commands for Modbus TCP/IP

The CLI commands of Modbus TCP/IP are listed as following table.
Feature

Command & example

Enable Modbus TCP

Switch(config)# modbus enable

Disable Modbus TCP

Switch(config)# modbus disable

Set Modbus interval time
between request

Switch(config)# modbus idle-timeout
<200-10000> Timeout vlaue: 200-10000ms
Switch(config)# modbus idle-timeout 200  set interval
request time out duration to 200ms.

Set modbus TCP master
communicate session.

Switch(config)# modbus master
<1-20> Max Modbus TCP Master
Switch(config)# modbus master 2  set maximum modbus
master up to 2; maximum support up to 20 modbus
communicate sessions.

Set modbus TCP listening port Switch(config)# modbus port

port Listening Port
Switch(config)# modbus port 502 ; default modbus TCP
service port is 502.