Humidity, Cleanness – H3C Technologies H3C S7500E Series Switches User Manual

Page 14

Advertising
background image

3

Temperature Range

Storage temperature

–40°C to +70°C (–40°F to +158°F)

Humidity

Maintain appropriate humidity in your equipment room, as described in

Table 2

.

Lasting high relative humidity tends to cause poor insulation, electricity creepage, mechanical
property change of materials, and corrosion of metal parts.

Lasting low relative humidity is likely to result in loose screws due to washer contraction, and even
electrostatic discharge (ESD), which causes the circuits to fail.

Table 2 Humidity requirements

Humidity Range

Operating humidity (noncondensing)

10% to 95%

Storage humidity (noncondensing)

5% to 95%

Cleanness

Maintain appropriate cleanness in your equipment room.

Dust is a hazard to the operating safety of your switch. Dust buildup on the chassis might result in
electrostatic adsorption, which causes poor contact of metal components and contact points,

especially when indoor relative humidity is low. In the worst case, electrostatic adsorption can

cause communication failure.

Table 3

shows the dust concentration limit in the equipment room.

The equipment room should meet limits on salts, acids and sulfides to eliminate corrosion and

premature aging of components, as shown in

Table 4

.

Table 3 Dust concentration limit in the equipment room

Substance

Concentration limit (particles/cu m)

Dust particles

≤ 3 x 10

4

(No visible dust on desk in three days)

IMPORTANT:

Dust particle diameter ≥ 5 μm

Table 4 Harmful gas limits in an equipment room

Gas Max.

(mg/m

3

)

SO

2

0.2

H

2

S 0.006

NH

3

0.05

Cl

2

0.01