INSPECTION AND MAINTENANCE

5.2.1 Troubleshooting Problems with Alarm Display

— 5-8 —

Status when Alarm Occurred

B

,

D

At power ON

During Servomotor

operation

A

,

B

,

C

Cause

Remedy

A

Servopack miscounted pulses or

malfunctioned due to noise.

Separate encoder wiring from main wiring

circuits turn ON Servopack power again.

B

Incorrect encoder wiring or poor

connection.

Check the encoder wiring and connectors

at encoder.

C

Encoder malfunctioned.

Replace Servopack.

D

Circuit board (1PWB) defective.

Replace Servopack.

8. A.b1

Display and Outputs

Digital Operator Display

Alarm Name

Alarm Output

A.b1

Reference input read error (for

speed/torque control only)

Output transistor is OFF

(alarm state)

Status when Alarm Occurred

A

,

B

During Servomotor

operation

At power ON

C

Cause

Remedy

A

Part malfunctioned in reference read-in

unit (A/D converter, etc.).

Reset alarm and restart operation.

B

Part defective in reference read-in unit

(A/D converter, etc.).

Replace Servopack.

C

Circuit board (1PWB) defective

Replace Servopack.

9. A.C1

Display and Outputs

Digital Operator Display

Alarm Name

Alarm Output

A.C1

Servo overrun

Output transistor is OFF

(alarm state)