APPLICATIONS

2.6.2 Servo Gain cont.

— 2-50 —

Cn-04 and Cn-05 are a speed loop gain and an in-
tegration time constant for the Servopack, respective-
ly.

The higher the speed loop gain value or the smaller the speed loop integration time constant
value, the higher the speed control response. There is, however, a certain limit depending on
machine characteristics.

These parameters are automatically set by the autotuning function.

The unit of speed loop integration time constant Cn-05 (Ti) can be changed to 0.01 ms.

Setting Position Loop

Set the following parameters related to position loop as necessary.

Cn-1A

POSGN

Position Loop Gain (Kp)

Unit:

1/s

Setting

Range: 1

to 200

Factory

Setting:

40

For Speed/Torque

Control and Position

Control

This parameter is a position loop gain for the Servo-
pack.

Increasing the position loop gain value provides posi-
tion control with higher response and less error. How-
ever, there is a certain limit depending on machine
characteristics.

This parameter is automatically set by the autotuning function.

Cn-1E

OVERLV

Overflow

Unit: 256

References

Setting

Range: 1

to 65536

Factory

Setting:

1024

For Position Control

Set in this parameter the error pulse level at which a
position error pulse overflow alarm (alarm A.31) is de-
tected.

If the machine permits only a small position loop gain
value to be set in Cn-1A, an overflow alarm may arise
during high-speed operation. In this case, increase
the value set in this parameter to suppress alarm
detection.

2

Speed

reference

Speed loop gain

Speed feedback

Position

reference

Position loop gain

Position feedback

Positions

Normal control

Error pulse

Cn-1E

OVERLV

(Alarm A.31)

(Alarm A.31)