2.2Setting Parameters According to Host Controller

— 2-11 —

Cn-01

Setting

Control Mode

Bit B

Bit A

Control Mode

0

0

Speed Control

This is normal speed control.

D

Speed reference is input from V-REF.

D

/P-CON signal is used to switch between P
control and PI control.

Servopack

Speed

reference

P/PI

changeover

(CN1-12)

(CN1-*1)

/P-CON

0

0

CN1-*1 is

open

PI control

CN1-*1 is at

0 V

P control

D

Torque reference input T-REF cannot be
used.

0

1

Zero-clamp Speed Control

This speed control allows the zero-clamp
function to be set when the motor stops.

D

Speed reference is input from V-REF.

D

/P-CON signal is used to turn the
zero-clamp function ON or OFF.

Zero-clamp

Zero-clamp is performed when

the following two conditions are

met:

Condition 1: /P-CON is turned

ON.
Condition 2: Motor speed drops

below the preset value.
Preset value: Cn-0F (ZCLVL)

Servopack

Speed

reference

(CN1-12)

(CN1-*1)

/P-CON

0

1

CN1-*1 is

open

Turns zero-clamp

function OFF

CN1-*1 is at

0 V

Turns zero-clamp

function ON

D

Torque reference input T-REF cannot be
used.

1

0

Torque control

For details on torque control, refer to 2.2.7 Torque Control.