2-58 / Installation & Operation

CI-ControlWave EFM

Table 2-18 - System Status LED Codes on System Controller Module

Status

In Hex

LED

6

LED

5

LED

4

LED

3

LED

2

LED

1

Indication

Definition

00 0 0 0 0 0 0

Application

Running

01 0 0 0 0 0 1

Unit

in

Diagnostic

Mode

03 0 0 0 0 1 1

Unit

Running

Diagnostics

04 0 0 0 1 0 0

Flash

XSUM

Error

05 0 0 0 1 0 1

Error

Initializing

Application

Device

07 0 0 0 1 1 1

Flash

Programming

Error

08 0 0 1 0 0 0

Using

Factory

Defaults

(flashed

at

start)

09 0 0 1 0 0 1

Battery

Failure

Detected

(flashed

at

startup)

0A 0 0 1 0 1 0

Currently

Loading

the

Boot

Project

0B 0 0 1 0 1 1

System

Initialization

in

Progress

10 0 1 0 0 0 0

Waiting

in

Recovery

Mode

11 0 1 0 0 0 1

Error

Testing

SDRAM

12 0 1 0 0 1 0

Error

Testing

SRAM

20 1 0 0 0 0 0

Application

Loaded

28 1 0 1 0 0 0

Stopped

at

a

Break

Point

30 1 1 0 0 0 0

No

Application

Loaded

38 1 1 1 0 0 0

Running

with

Break

Points

3B 1 1 1 0 1 1

Waiting

for

Power-down

(after

NMI)

3E 1 1 1 1 1 0

Waiting

for

Updump

to

be

Performed

3F 1 1 1 1 1 1

Unit

Crashed

(Watchdog

Disabled)

Figure 2-47 - SCM Status LED Hexi-decimal Codes

(See Table 2-18 for Definitions)


2.4.2.3 Remote Upgrade of ControlWave EFM Firmware

It is possible to download system firmware into an unattended remote ControlWave EFM.
This function can only be accomplished if CPU Board Switch SW2-6 (associated with the
unit in question) is set in the ON position (factory default). The procedure for performing a
remote download of system firmware is discussed in Appendix J of the Open BSI Utilities
Manual (document D5081). Note: Remote Upgrade of ControlWave EFM Firmware
requires Boot PROM version 4.7 or higher and System PROM version 4.7 or
higher.