The commons associated with each form C Relay (R0COM and R1COM) have the option of
being tied to the ControlWave EFM Power Ground or to a floating Ground. Jumper W1 is
associated with Outputs R0A and R0B and W2 is associated with outputs R1A and R1B.
When Jumper W1 is installed the common (C) associated with Outputs R0A and R0B is tied
to ControlWave EFM Power ground; when Jumper W1 is not installed, the common will
be floating. When Jumper W2 is installed the common (C) associated with Outputs R1A and
R1B is tied ControlWave EFM Power ground; when Jumper W2 is not installed, the
common will be floating.

Table 2-14 - Jumper Settings versus Form C Relay Output States

JUMPERS

W3/W5

R0A

STATE

JUMPERS

W4/46

R0B

STATE

JUMPERS

W7/W9

R1A

STATE

JUMPERS

W7/W9

R1B

STATE

IN/OUT NO IN/OUT NO IN/OUT NO IN/OUT NO
OUT/IN NC OUT/IN NC OUT/IN NC OUT/IN NC


Table 2-13 provides the relationship between Jumper settings and Form C Relay Outputs.

Table 2-15 - Digital To Relay I/O Board Connections to J1/P1

J1 Pin

Signal

Function

Wiring Connections

1

R1B

Relay 1 Output B

To Field

2

R1A

Relay 1 Output A

To Field

3

R1COM

Relay 1 Common

To Field (See W2)

4

CHASSIS GND Chassis Ground

CWMICRO Chassis Gnd. Lug

5

R0COM

Relay 0 Common

To Field (See W1 - Section 1.1.1)

6

ROB

Relay 0 Output B To Field

7

ROA

Relay 0 Output A

To Field

8 -

-

-

9

POWER GND

Power Ground

Pwr. Dist. Bd.

TB4 Pin 2 (Black Wire)

10

POWER - DC

Power - 6/12 Vdc

Pwr. Dist. Bd.

TB4 Pin 1 (Red Wire)

11

DOUT0

Discrete Output 0 DI/O Module TB2-5 - TB2-8 or

Mixed I/O Module TB1-1 - TB1-6 (Yellow Wire)

12

DOUT1

Discrete Output 1 DI/O Module TB2-6 - TB2-8 or

Mixed I/O Module TB1-2 - TB1-6 (Orange

Wire)


The DI/DO Module and the Mixed I/O Module provide independently firmware controlled
open drain outputs, which can be used for control or signaling functions (DI/DO Modules
provide up to four DO while the Mixed I/O Module provides up to 6 DO). Each output is
wired to the source terminal of an N Channel MOSFET capable of switching up to 16 Volts
at up to 100mA. When closed, the FET shorts the output to ground with resistance of .5
Ohms or less. These outputs are protected by 16V Transorbs. Since these outputs are not
isolated, caution must be exercised to ensure that the load current does not affect operation
of the ControlWave EFM or related devices.

Two of these outputs may be wired to field circuitry via the Digital to Relay I/O Board
option (see Figure 2-28). Table 2-15 provides the wiring connections for the DI/O Module or
the Mixed I/O Module and the Digital to Relay I/O Board.