background image

CI-ControlWave EFM

Specifications / 4-7

2 High Speed Counter Inputs per Module

1 Analog Output (optional) per Module


Terminations:

Pluggable - Max. wire size is 14 gauge


Power Consumption:

5mA Base Current @ 3.3V

Non-isolated Mixed I/O Module Digital Inputs/Outputs

Number of Points:

Up to 6 individually jumper configurable DI/O


Input Current:

Individually Jumper selectable input current of 60uA or
2mA


Input Configuration:

Internally Sourced Dry Contact


Input Filtering:

30 milliseconds


‘0’ State Voltage:

below 1.5V


‘1’ State Voltage:

above 1.5V


Bus Access:

Eight Bits Wide


Surge Suppression:

31V Transorb between signal and ground

Meets ANSI/IEEE C37.90-1978


Status Indication:

None


Output Configuration:

Open Drain (Externally Powered)


Max. DO Load Current:

100mA @ 31Vdc


Electrical Isolation:

None


Power Consumption:

Add: 66uA or 2mA for Each ON DI (Jumper Selectable per
Point)

Non-isolated Mixed I/O Module Analog Inputs


Number of Inputs:

4 Single Ended Inputs (1-5V or 4-20Ma) individually
jumper configurable


Input Type:

(Externally Powered) Voltage Input: 1-5 Vdc
(Externally Powered) Current Loop: 4-20mA

Input Impedance:

1 Meg ohm for 1-5V inputs

250 ohm for 4-20mA inputs


Accuracy:

0.1% of Span @ +25ºC (+77ºF)

0.2% of Span @ -40ºC to +70ºC (-40ºF to 158ºF)


Conversion Time:

20 microseconds