Power Consumption:

2.5mA + 1.145mA @ 4.66US/Channel Period, CLK active

180uA, CLK stopped

Non-isolated Mixed I/O Module Analog Output


Number of Outputs:

1 AO (1-5V or 4-20Ma) jumper configurable


4-20mA Output
Compliance:

250 ohm load with 11V External Power Source

650 ohm load with 24V External Power Source


1-5V Output:

5mA maximum output current into external load with
external voltage range of 11 to 30 Vdc


Accuracy: Current

Output:

0.1% of Span @ +25ºC (+77ºF)

0.2% of Span @ -20ºC to +70ºC (-4ºF to 158ºF)

0.3% of Span @ -40ºC to +70ºC (-40ºF to 158ºF)
Voltage Output Compliance (I

load

max = 5mA):

(see Note

1

& Note

2

)

0.1% of Span + X @ +25ºC (+77ºF)
0.2% of Span + X @ -20ºC to +70ºC (-4ºF to +158ºF)
0.3% of Span + X @ -40ºC to +70ºC (-40ºF to 158ºF)
where X = [(2.5 ohms x I

load

)/4.4V x 100]

Note

1

: Does not include error due to inductors

Note

2

: 2.5 ohm uncompensated series resistance with

Inductors


Power Consumption:

System Power - 5.0mA from 3.3V source

External Power V to I (AO at 20mA each) - 24.3mA

External Power V to I (AO at 5V @ 0mA) – 4.2mA

External Power V to I (AO at 5V @ 5mA) - 9.2mA

Non-isolated Mixed I/O Module High Speed Counter Inputs


Number of Inputs:

2 HSC Inputs per Module


Input Configuration:

Internally Sourced Dry Contact, individually Jumper
selectable Debounce Circuitry and individually Jumper
selectable input current of 180uA or 2.2mA. HSC Circuitry
can be Jumper Enable/Disabled to save power


Input Frequency:

10kHz Max.


Input filtering:

20 microseconds


Signal Conditioning:

Debounce circuit for contact closures and bandwidth
limiting


‘1’ State Voltage:

below 1.5V

‘0’ State Voltage:

above 1.5V


Bus Access: