3-12 / Service

CI-ControlWave EFM

COM2: From the factory, RS-232 Communications Port COM2 on the CPU Board defaults

to 9600 baud, 8-bits, no parity, 1 stop bit, BSAP/ControlWave Designer protocol
operation. To test COM2 using the WINDIAG program, it must not otherwise be in
use and CPU Switch SW2-8 must be set OFF.


COM3: RS-485 Communications Port COM3 on the CPU Board defaults to 9600 baud, 8-

bits, no parity, 1 stop bit, BSAP/ControlWave Designer protocol operation. To test
COM3 using the WINDIAG program, it must not otherwise be in use and CPU
Switch SW2-8 must be set OFF. In lieu of the use of an RS-232 Port, an RS-485
cable (see Tables 2-3 & 2-5) can be connected between COM3 and the PC’s RS-485
Port.


COM4: From the factory, RS-232 Communications Port COM4 on the first optional

Expansion Communications Module defaults to 9600 baud, 8-bits, no parity, 1 stop
bit, BSAP/ControlWave Designer protocol operation. To test COM4 using the
WINDIAG program, it must not otherwise be in use and CPU Switch SW2-8 must
be set OFF. When required, an RS-232 “Null Modem” cable be connected between
COM4 and the PC (typically COM1) (see Figure 2-12).


COM5: RS-485 Communications Port COM5 on the first optional Expansion

Communications Module defaults to 9600 baud, 8-bits, no parity, 1 stop bit,
BSAP/ControlWave Designer protocol operation. To test COM5 using the
WINDIAG program, it must not otherwise be in use and CPU Switch SW2-8 must
be set OFF. In lieu of the use of an RS-232 Port, an RS-485 cable (see Tables 2-3 &
2-4) can be connected between COM5 and the PC’s RS-485 Port.


COM8: From the factory, RS-232 Communications Port COM8 on the second optional

Expansion Communications Module defaults to 9600 baud, 8-bits, no parity, 1 stop
bit, BSAP/ControlWave Designer protocol operation. To test COM8 using the
WINDIAG program, it must not otherwise be in use and CPU Switch SW2-8 must
be set OFF. When required, an RS-232 “Null Modem” cable be connected between
COM8 and the PC (typically COM1) (see Figure 2-12).


COM9 RS-485 Communications Port COM9 on the second optional Expansion

Communications Module defaults to 9600 baud, 8-bits, no parity, 1 stop bit,
BSAP/ControlWave Designer protocol operation. To test COM9 using the
WINDIAG program, it must not otherwise be in use and CPU Switch SW2-8 must
be set OFF. In lieu of the use of an RS-232 Port, an RS-485 cable (see Tables 2-3 &
2-4) can be connected between COM9 and the PC’s RS-485 Port.


To use the WINDIAG program place any critical process (associated with the Control-
Wave EFM unit in question) under manual control. WINDIAG cannot be run while the
ControlWave EFM application is running. Set the CPU Modules Switch SW2-8 to the OFF
position. Perform steps 1 through 6 below.

1. Start the OpenBSI NetView Program. A menu similar to Figure 3-7 will appear.

2. To start the WINDIAG program, go to the Start Program’s menu, select OpenBSI Tools,

then select Utilities Programs and then select Diagnostics.

3. Once WINDIAG has been entered, the Main Diagnostics Menu of Figure 3-8 will

appear.