ControlWave EFM

Special Instructions for Class I, Division 2 Hazardous Locations

10/06/2006

Appendix A, Document CI-ControlWave EFM

Page 2 of 2

Table A1 -Module/Board Connector Customer Wiring Connectors (Continued)


Module/Item Connector

Wiring

Notes

SCM Module

TB1 - Input Power

Typically Factory Wired - *

SCM Module

TB2 - RTD Interface

Field Wired - Refer to ¶ 9 of this document.

Exp. Comm Module 1

J4 - COM4, 9-pin Male D-sub

RS-232

J5 - COM5, 9-pin Male D-sub

RS-485

Remote Comm. Port: For Radio or external

Network Comm. Refer to Model Spec. and ¶ 10

of this document. When used for Network

Comm., use Div. 2 wiring methods. If COM4 is

used in conjunction with a radio/modem refer

to 11 of this document.

Exp. Comm Module 1

J8 - COM7, RJ11 Female

Modular connection to Phone Co. equipment.

Exp. Comm Module 2

J4 - COM8, 9-pin Male D-sub

RS-232

J5 - COM9, 9-pin Male D-sub

RS-485

Remote Comm. Port: For Radio or external

Network Comm. Refer to Model Spec. and ¶ 10

of this document. When used for Network

Comm., use Div. 2 wiring methods. If COM8 is

used in conjunction with a radio/modem refer

to 11 of this Document.

Exp. Comm Module 2

J8 - COM11, RJ11 Female

Modular connection to Phone Co. equipment.

Refer to ¶ 6, 7, 8 & 11of this document.

Analog I/O Module

TB1/TB2 - 10-pin Term. Blocks Field I/O wiring connectors are unrated; use

Div. 2 wiring methods. *

Digital I/O Module

TB1/TB2 - 10-pin Term. Blocks Field I/O wiring connectors are unrated; use

Div. 2 wiring methods. *

HSC Input Module

TB1/TB2 - 10-pin Term. Blocks

Field Input wiring connectors are unrated;

use Div. 2 wiring methods. *

Mixed I/O Module

TB1/TB2 - 10-pin Term. Blocks Field I/O wiring connectors are unrated; use

Div. 2 wiring methods. *

Digital To Relay I/O Bd.

J1 10-pin In-line Connector

Field I/O wiring connector is unrated, use Div.

2 wiring methods. Refer to ¶ 12 of this

document. *

Power Distribution Bd.

(see ¶ 5 - this document)

TB1 - 3-pin Term Block

TB2 - 2-pin Term Block

TB3 - 2-pin Term Block

TB4 - 2-pin Term Block

TB5 - 2-pin Term Block

TB6 - 2-pin Term Block

Primary Power Input - User wired *

Main Power Out 1 - Factory wired *

Main Power Out 2 - Factory wired *

Fused Power Out 1 - Factory wired *

Fused Power Out 2 - Factory wired *

Fused Power Out 3 - Factory wired *

21V Power Supply Bd.

(see ¶ 5 & 13 of

this document)

TB1 - 3-pin Term Block

TB2 - 4-pin Term Block

12V Power Input - Factory wired *

21V Transmitter Power -Field Wired

TB2 is unrated, use Div. 2 wiring methods.

Enclosure Bottom

Local Port Circular Connector

Local Comm. Port - Factory Wired. Refer to ¶

3 of this document. *

Note: * =

These wires should only be installed/removed when the item (PCB) in question is

installed/removed or when checking wiring continuity. The area must be known to be

nonhazardous before servicing/replacing the unit and before installing or removing PCBs,

Connectors or individual I/O or Power wires. Refer to

6, 7 & 8 of this document. All input

power and I/O wiring must be performed in accordance with Class I, Division 2 wiring

methods as defined in Article 501-4 (b) of the National Electrical Code, NFPA 70, for

installations within the United States, or as specified in Section 18-152 of the Canadian

Electrical Code for installation in Canada.