Emerson Process Management ControlWave EFM 3808 User Manual

Page 174

Advertising
background image

D-4 / Appendix D - Radio/Modem Installation Guide

CI-CW MICRO/CW EFM

4. Open Hyperterminal on the PC and set the PC communication port settings as follows:

Bits per second: 19200
Data bits:

8

Parity:

None

Stop bit:

1

Parity Check:

None/Off

Carrier Detect: None/Off
Flow Control:

Xon/Xoff


5. Cycle power to the ControlWave MICRO/ControlWave EFM. The FreeWave

configuration menu will appear in Hyperterminal.


6. In the configuration menu, set the radio as a multipoint slave. Go to the edit book and

type in the serial number of the Master Radio to which you want to communicate. Make
sure the Baud Rate matches that of the Master Radio. Once settings have been
implemented, press the Esc Key to exit the configuration menu.


7. Set Expansion Comm. Module Configuration Jumper JP2 into a storage position, i.e.,

parked (no connection).


8. Using Hyperterminal at the Master Radio, inter configuration mode and set the radio as

a multipoint master. Using the edit book (in configuration mode) make sure that no
serial number is set. Verify that the baud rate matches that of the Slave Radio.

(Looking into

Wire Terminal Side

of

Cable Connectors)

3 = TXD

6 = DSR

7 = RTS

8 = CTS

4 = DTR

2 = RXD

1 = DCD

5 = GND

To P2 Pin-4

To P2 Pin-2

To P2 Pin-7

To P2 Pin-3

To P2 Pin-6

To P2 Pin-5

To P2 Pin-1

PC

9-Pin Female

“D” Connector

P1

CW u/CW EFM

9-Pin Female

“D” Connector

P2

3 = TXD

6 = DSR

7 = RTS

8 = CTS
4 = DTR

2 = RXD

1 = DCD

5 = GND

or

vice

versa

Figure D3 - (Internal Radio/Modem Configuration) BBI P/N 392843-01-3

Full-duplex Null Modem Cable Diagram

D1.1.3 Installing an Internal MDS Transnet OEM Radio


MDS Transnet OEM Radio is provided (for user installation) in a kit consisting of the
following components:

• 6-32 x .188” Pan Head Screw (Qty. 4) - Fig. D4 Reference = 1
• 6-32 x .313” F/F Standoff (Qty. 4) - Fig. D4 Reference = 2
• 6-32 x .250” Pan Head Screw (Qty. 4) - Fig. D4 Reference = 3
• MDS Transnet Radio Cable (with Nut and Washer- Fig. D4 Reference = 4
• Swaged Standoff (Qty 4) - Built into CPU/System Controller Bd. - Fig. D3 Reference = E
• MDS Transnet Radio Module - Fig. D5 Reference = 5