Emerson Process Management ControlWave EFM 3808 User Manual

Page 271

Advertising
background image

Section 3 - Grounding & Isolation

Page 3-3

S1400CW

ground has been established, it should be tested on a regular basis to preserve system
integrity.

Figure 3-2 - Basic Ground Bed Soil Test Setup


Figure 3-3 - Basic Ground Bed Soil Test Setup with Additional Ground Rods


Figure 3-2 shows the test setup for ‘Good Soil’ conditions. If the Megger* reads less than 5
ohms, the ground is good. The lower the resistance, the better the earth ground. If the

Advertising
This manual is related to the following products: