Emerson Process Management ControlWave EFM 3808 User Manual

Page 137

Advertising
background image

CI-ControlWave EFM

Specifications / 4-5

Note

2

: 2.5 ohm uncompensated series resistance with

Inductors

Terminations:

Pluggable - Max. wire size is 14 gauge

Data Transfer:

8 Bit Wide bus access

4.4.2 Non-isolated Digital Input/Output Module


Non-isolated Digital Inputs

Number of Inputs:

12 DI individually jumper configurable for 2mA or 60uA
Internally Sourced (Dry Contact) operation


Input Filtering:

15 milliseconds


Input Current:

Jumper configured for 2mA or 60uA nominal


‘0’ State Voltage:

below 1.5V


‘1’ State Voltage:

above 1.5V


Bus Access:

Eight Bits Wide


Electrical Isolation:

None


Surge Suppression:

31V Transorb between signal and ground

Meets ANSI/IEEE C37.90-1978


Status Indication:

12 LEDs (one per point)

Non-isolated Digital Outputs


Number of Outputs:

4 DO


Output Configuration:

Open Drain (Externally Powered)


Maximum Load Current:

100mA @ 31Vdc


Bus Access:

Eight Bits Wide


Electrical Isolation:

None


Surge Suppression:

31V Transorb between signal and ground

Meets ANSI/IEEE C37.90-1978

General DI/DO Module Specs.


Power Consumption:

Status LEDs Disabled

1.3mA @ 3.3Vdc: 12DIs OFF, CLK stopped

2.1mA @ 3.3Vdc: 12DIs ON @ 66uA, CLK stopped

25.3 @ 3.3Vdc: 12DIs ON @ 2mA, CLK stopped

3.6mA @ 3.3Vdc: 12DIs OFF, CLK active