4.4

mA @ 3.3Vdc: 12 DIs ON @ 66uA, CLK active

27.6mA @ 3.3Vdc: 12 DIs ON @ 2mA, CLK active

Status LEDs Enabled

All DIs and DOs OFF: 33uA

All DIs and DOs ON: add 32mA

Terminations:

Pluggable, max wire size is 14 gauge for local terminations -
Two 14-pin mass termination headers are provided for
remote terminations

4.4.3 Non-isolated High Speed Counter Input Module


Number of Inputs:

4 HSC Inputs per Module


Input Configuration:

Internally Sourced Dry Contact, individually Jumper
selectable Debounce Circuitry and individually Jumper
selectable input current of 200uA or 2mA


Input Frequency:

10kHz Max.


Input filtering:

20 microseconds


Signal Conditioning:

Debounce circuit for contact closures and bandwidth
limiting


‘1’ State Voltage:

below 1.5V

‘0’ State Voltage:

above 1.5V


Bus Access:

Eight Bits Wide


Electrical isolation:

None

Surge Suppression:

31V Transorb between signal and ground
Meets ANSI/IEEE C37.90-1978


Terminations:

Pluggable, max wire size is 14 gauge for local terminations -
Two 14-pin mass termination headers are provided for
remote terminations


Status Indication:

4 LEDs (one per point)


Power Consumption:

3.9mA IOCLK stopped (All Inputs OFF)

6.8mA IOCLK running (All Inputs OFF)

Additional Current per Input

200uA or 2MA per HSCSET or HSCRST Input (ON State)

2mA per ON LED

33uA for LED circuitry

4.4.4 Non-isolated Mixed Input/Output Module


Number of I/Os:

6 jumper configurable DI/DOs per Module

4 Analog Inputs per Module